    i4 Series UPS MODULE

     
Item

Specification

Remarks
   Mains supply
Voltage
415, 3ph, 3W+ PE
+10%, -15%
Neutral NOT required
Frequency
50Hz, +/- 6%
 
Power Factor
0.8 – for 6 pulse rect
0.8 for 12 pulse rect
Typical values at rated I/P voltage and 100% load on inverter.
Recommended fuse at input feeder
2X of rated input current.
For Battery back-up more than 60 min – fuse of higher capacity may be required – consult factory.
Recommended feeder KVA
Minimum 2X of rated output KVA.
For Battery back up more than 60 min the input feeder rating may be higher – consult factory.
   Alternate / Bypass supply
Voltage - 1ph bypass nominal value = Input voltage, +/- 10%
Frequency 50Hz, +/- 6%
   Battery / DC link
DC link voltage range
305 - 430 VDC
DC OV trip at 435 V
DC UV trip factory set for type of battery
Max DC Bus ripple
2% RMS (W/O battery )
1% RMS (With battery)
 
Number of cells
(Lead - Acid)
176 ---180
Inverter to be electrically disconnected for initial charging.
Number of cells
(Ni-Cad)
277
Inverter to be electrically disconnected for initial charging.
   Output
Voltage
110/115/120/220/230/240
1ph – 2W + P
O/P Neutral can be grounded.
For other voltages – consult factory.
230V o/p is default.
Regulation (Inverter) +/- 1% - Steady state load
+/- 5% for 100% step loading
< 1 cycle recovery to 98%.
Frequency 50Hz, +/- 0.1% - Free running
50Hz, +/- S% - Bypass sync (S = 1/2/3/4/5/6)
Slew rate 0.1Hz/sec or 1Hz/sec pre-selected.
Waveform Sinusoidal - THD <3% Linear loads
- THD <5% Nonlinear loads (CF: 3)
Load PF range 0.6 PF to Unity within the rated KVA & kW.
Standard ratings KVA (KW) (For Intermediate ratings-consult factory) 5(4),7.5(6) , 10(8) , 15(12) , 20(16) 30(24) , 40(32) , 50(40), 60(48),75(60),100(80),120(96)
Overload 150% - 60 sec’s, -125% - 600secs
Fuse clearing
(< ¼’th cycle)
30 % rated semiconductor type (GSG).
10 % rated high-speed HRC (NS).
Inverter DC-AC conversion efficiency 92% for single Module 90% for parallel system.
Potential free alarm contacts
For remote signaling
5 nos. 230V 1A change over contacts – field programmable (assignable) to any available alarm.
Indication
LED indication on UPS module
Mains ON, Bypass ON, Inverter ON, Static switch Position, Common Alarm, Float, Boost, Battery Isolate.
   Cabling
Entry Bottom (Standard) TOP (Optional) one addition cubicle for top cable ally.
   Enclosure
Degree of Protection
IP31/41
IP31/41
Module Dimensions H*W*D mm (aprox)
upto 30KVA
Above 30KVA
Finish Similar to RAL7032. (other shades on request)
   Operating conditions
Operating temperature range 0° to 45° 0° to 50° (OPTIONAL)
Storage temperature range -10° to 55°
Atmosphere Non corrosive, dust free
Freely ventilated – capable of maintaining ambient temperature within specified limits.
Heat loss (for ventilation / air conditioning calculation) Depends upon system configuration (consult factory)
Altitude Upto 1000 Mts. From MSL.
Humidity 95% RH – non-condensing.
Ventilation Units have integral fans
Audible noise @ 1mts dbA
Up to
7.5KVA
<55dbA
<60dbA for fan redundancy
10-20KVA
<58dbA
<65dbA for fan redundancy
25-30KVA
<65dbA
Above 30KVA <70dbA
   Ui4 –01  
Enclosure color and IP
Other than STD color and IP
Any available color – Specify. (Confirm delivery time for colors other STD color before commitment)
IP 20, 30,40 and 53.
   Ui4 –02  
Redundant fans
Fan redundancy for units upto & including 80KVA only
Each fan will be provided with a redundant fan. (Both primary & redundant fans will run simultaneously)
   Ui4 –O3
Indications
Other than STD on UPS Module
Mains R, Y, B indications, Charger Fail, Float ON, Boost ON, Fuse Fail, Fan Fail, Load on manual bypass.
   Ui4 –O4
Potential free alarm contacts
Other than STD on UPS Module
Charger Fail, Fuse Fail, Fan Fail, Load on manual bypass
   Ui4 –O5
Automatic
Server shutdown
DB9 port – RS232C of Server.
Automatic shutdown of target server via DB9 – RS232C link – initiated upon Mains Fail/ Low Batt.
Requires loading of SEC software (exact details of target operating system & version required).
Uses up 2 relay contacts of Ui4-03 option.
Server – UPS length < 20mts.
Consult factory with details before making a commitment.
   Ui4 –O6
MCR unit
Monitoring
Control
Reporting
PC based monitoring, Control & report generation for single or Redundant configurations.
Includes Software + Manual + Connecting cable.
Requires min. one PC with 2 serial port + Printer.
(consult factory for specific details)
   Ui4 –O7
MODBUS protocol
Monitoring
Control
Reporting
RS485 connectivity.
Server to UPS length up to 1000 meters.
Memory map will be given to customer for making front end program for parameter monitor on PLC/DCS/SCADA
   Ui4 –8
SNMP protocol
Monitoring
Control
Reporting
RJ45 connection.
Connection through Ethernet card.
SNMP card is an interface to the Ethernet network and provide us UPS information via the standard SNMP protocol
Safe shut down of server possible through this protocol.
UPS information gets from each PC which is connected in network
   Ui4 –09
BMS
Battery Monitoring System
One BMS for One Battery bank.
Monitor battery back up time.
Monitor Charging time
Auto battery test
Monitor Battery volt and current
   Ui4 –10
I/P isolation transformer.
Protection against Ground Fault on DC side
•For 5KVA next higher size Cubical Required.
UP to 30KVA one additional Matching cubical required for SA/PR system.
For 40-50KVA One additional cubical for SA and TWO addition cubical for PR system.
Above 50KVA no additional Cubicle.
   Ui4 –11
UPS with 12 pulse Rectifier.
Lower I/P Current harmonics contains.
Up to 50KVA one additional cubical for each UPS module.
Above 50KVA no additional cubical.
   Ui4 –12
20 battery DC link
194-315VDC
No of cell for SMF and LATB :108-120
No of cell for Ni-cd : 176-186
   Ui4 –13
Metering
Rectifier O/P
Rectifier o/p Analog meter.
   Ui4 –14
Switch Gear
For Isolation
Upto 20KVA (except 110V o/p) Isolators provided at Mains I/P, Bypass I/P, Battery I/P and UPS O/P.
Above 20KVA MCCBs are standard.
Battery reverse polarity protection is optional feature.
Specify fault level if requirement is more then 10KA.
   Ui4 –15
Harmonics Filter
Reduce current harmonics
For 6 pulse rectifier suggested filter is 5TH and 7th
For 12 Pulse rectifier suggested filter is 11th and 13th
For Cubical size contact HO
   Ui4 –16
Space Heater
Utility option
Standard ulility box having lamp.
 
Structure Details For single Module.
     
Module dimensions ( mm)
KVA
KW
Typical Inverter
      Efficiency

Height
Width
Depth
5
4
92%
1300
700
750
7.5
6
92%
1300
700
750
10
8
92%
1300
700
750
15
12
92%
1500
700
750
20
16
92%
1500
700
750
30
24
92%
1900
850
850
40
32
92%
1900
850
850
50
40
92%
2400
850
850
60
48
92%
2400
1650
850
75
64
92%
2400
1650
850
100
80
92%
2400
2450
950
120
100
92%
2400
2450
950

  Note:

 50KVA 110V o/p System: 2300 x 1650 x 850
 Canopy height is 403 mm for 1300 and 1500-mm height structure.
 Total height including canopy is 1703 and 1903 mm.
 Canopy height is 416 mm for 1800-mm height structure.
 Total height including canopy is 2216 mm.
 For input isolation separate cubical required up to 50KVA system.

 

 
 
 