Sitemap Feedback Contact
 
Home Organisation Strategic business units Products & Services Customer Support Client List Approvals

 
     UPS
     Drives and Automation
     Railway Products
     Embedded Systems
     Utility Support
   Equipments
       Gauscor
       Turbo-Tech
         Energy Conservation
   Turbine
         FAQ ECT
         Low Cost Gas Turbine
    FAQ on Energy Conservation Turbine ECT – (50 – 315 kW)
 


Fluctuating steam load ?

Induction generator never trips due to steam load fluctuations unlike an alternator. The power generator will vary in proportion to the steam flow rate. If steam flow rates falls below a critical value (say<20% of designed value) the IG will go into motoring mode.

Fluctuations in inlet steam pressure ?
Induction generators continue to operate in spite of large fluctuations in inlet pressure unlike an alternator. The power generator will vary in proportion to the pressure at inlet. If it falls below as critical value(say<50% of designed value),the IG will go into motoring mode.

Paralleling with a DG set ?

It is possible as long as DG governor is stable and DG power rating is atleast 30% greater than IG.

Break-up of cost ?

 
Turbine module 35%
Gear box module 25%
Induction Generator 20%
Controls and instrumentation 10%
Mounting skid and miscellaneous 10%

How to control power factor ?

Power factor will be corrected at site depending upon the client's existing capacitor bank and existing power factor. We will provide banks of 10KVAR and keep adding as necessary at the time of installation to bring the P>F better than 0.85 lag.
Is water quality a problem ?
For saturated steam applications no particular care is needed as all the dissolved salts will be in the boiler. If it is good for the boiler, it will be acceptable to the turbine also. Further since we are using hardened stainless steel for the turbine, effects of erosion and corrosion are minimal. In case of super heated steam, silica content needs to be monitored closely (less than 1ppm).
Life of turbine ?
15 Years since we are using hardened stainless steel for the turbine rotor
Time between overhauls ?
It is estimated to be 3 years or more, with an annual inspection.
What about spares and maintenance ?
We recommended the following.
 
Bearings and seals Annual inspection and change if necessary
Lube oil change Every three years
  Some fast moving and low cost spares like oil filters, gaskets, fuses, relays, etc. will be handy and the same will be advised during installation.
  It is advisable to order for one set of bearings and seals along with the turbine.
Life on saturated steam ?
It is expected to be 15 years since we are using hardened stainless steel for the turbine rotor. However adequate care is to be taken to ensure that only dry steam enters the turbine and this can be simply accomplished by installing an efficient moisture saperator (with thermodynamic trap) and a Y-strainer in the inlet line to the turbine. This is not included in standard scope of supply.
Super cooled vapor.
The steam existing the nozzle will be in a super cooled state and the passage through the turbine takes less than a milli-second. It takes about 1 to 2 secs, for condensation to occur and all the condensation will occur down stream of turbine, hence not harmful to the turbine. In addition, since it is a hardened stainless steel blisk, there is no erosion on saturated steam.
How an induction Generator works ?
Whenever an induction motor is run higher than its synchronous speed by the help of a prime mover it starts generating power instead of absorbing power. All induction machines always operate at a lagging power factor (i.e, the current vector lags the voltage vector and the cosine of the angle of the lag is defined as the power factor).The power factor depends on the slip which is a function of the loading of the motor. The lag angle will be 90 deg when the machine runs at zero slip, that is at synchronous speed and this is known as quadrature. At quadrature, it will neither absorb nor generate power. If with the help of a prime mover such as the turbine, the speed is increased beyond synchronous, the lag angle increases beyond 90 degrees and the power factor becomes negative. Therefore the power, i.e. VI CosØ will be negative which means the machine is generating power. The power factor is adjusted by adding the required KVAR capacitor bank.

Since the excitation of the IG is from the grid, it does not require any governing. Grid acts as the governor. Also it does not calls for synchronizing as it automatically locks itself to the grid.
Safety interlocks ?
ECT is wired to shut down safely in the any of the following undesirable operating conditions.
 
High lube oil temp.
Low lube oil pressure.
Low air pressure (to valve actuator).
Over speed (which is unlikely).
Over voltage.
High winding temp.
Earth leakage.
Over load.
The trip will be annunciated and a hooter will come `ON` and one has to accept and reset before restarting.
In addition an emergency trip (Mushroom button switch) is also provided.
Advantages of high speed ?
ECT is a high speed turbine. Following are the merits.
 
For a given enthalpy drop, the turbine diameter is small.
Hence for a particular mass flow, the arc of steam admission will be larger
This results in lower losses caused by partial admission.
This enhances the adiabatic efficiency of the turbine.
Means higher power for the same steam parameters.
Alternator Vs Induction generator ?
Induction generator has the following advantages.
 
IG does not require a governor, the associated governing valve and actuator
No synchronizing.
No load management is required. No load shedding under any steam demand condition.
Can accept wide fluctuations in steam flow and inlet pressure.
Makes most effective use of process steam flow, maximizes power generation.
Can ECT take a mechanical drive?
It is possible to drive but would require a governor to control the speed of the driven equipment. We will quote on a case by case basis.
Reverse power relay ?
Induction generator does not need a reverse power relay. Since the chances of going into motoring mode are so infrequent and as grid power is essential during starting, reverse power relay is not recommended. If the client insists, the same can be implemented at extra cost. Please be reminded that this will have to be bypassed during starting and operational manpower cost will go up. IG does not require any attention and it is a ` fit and forget ` system.
 

Highlights of ECT Turbines.
 
  High speed - high efficiency turbine, 60% of isentropic enthalpy drop to electrical power.
  Customized design, maximum efficiency for a given steam conditions.
  Low noise, high efficiency gearbox.
  Pressurized lube oil circulation system.
  Hardened stainless steel turbine and SS casting for all steam wetted parts. Hence frequent starts possible.
  Inherent design safety to ensure that the turbine can never cause any ballistic damage due to over-speeding. This is accomplished by
 
Proper choice of turbine material of high strength and elongation
Maintaining very tight clearance between turbine tip and shroud so that the turbine can at worst rub the shroud and come to a screeching halt and cause no damage to the personnel if present near the turbine.
SS shroud of the turbine act as a containment enclosure which has a very high elongation of 70% before rupture
  Designed to handle saturated steam.
  Life of turbine virtually unlimited.
  Zero leakage sealing system, preventing steam leakage losses of nearly 3 to 4 lakh rupees annually.
  Lightweight, skid mounted with AVM`s, no foundation necessary, no cost to customer on civil works, faster installation time.
  High power to weight ratio.
  Use of induction generator eliminates governor. It automatically synchronizes with the grid and no load management is called for. It allows maximum exploitation of steam potential available at a client’s works.
  “Fail safe” interlocks to ensure safety of equipment.
  Can accept pressure fluctuations at inlet and varying steam flows with out tripping.
  Total service support and fast response to service calls.
 
     
   Copyright 2007 Hi-Rel Electronics Limited
   All rights reserved
News & Events What's new Careers Feedback Sitemap Contacts
  Powered by : netservicesindia